Optimizing Airflow and Capture Efficiency

Innospec’s Buildings 4 and 7 suffered from poor airflow and fume capture. Kogi’s assessment found three core issues: an exhaust fan delivering only 5,000 CFM against an 8,250 CFM requirement, ductwork reduced from 18″ to as small as 8″, and hood gaps letting mist escape. The plan restores original duct sizes, adds stainless hood extensions and strip curtains, and replaces the fan with a stainless steel blower rated 8,250 CFM at 11″ SP with VFD control. Paired with monthly maintenance, the upgrade restores full system performance and keeps the facility ahead of OSHA and EPA requirements.